Superheat Explained
Checking
and setting superheat at commissioning is important to ensure the efficient
running and long life of the equipment. This is critically important with split
systems to ensure that the refrigerant volumes are correct particularly where
additional refrigerant charge is required.
Whilst
modern air conditioning equipment makes checking Superheat as
simple as plugging a "Service Interface” or reading the
built in display on PLC control board, there is
still plenty of equipment in the field with older style control systems that
require the manual superheat testing process outlined below.
So what exactly is superheat?
Superheat
is an indication of the amount of extra heat (or superheating) the refrigerant
vapour has received after it has passed through its latent phase in the heat
transfer coil.
Why is correct superheat so important?
The
compressors lifespan!! If the superheat is set right then there is no reason
why the compressor won’t run for twenty or more years. If it’s not set right
and the compressor is flooding or starving excessively, then expect as little
as a year or two before failure. The compressor needs the correct amount of
returning refrigerant to keep its motor windings at the correct temperature and
most importantly its oil at an optimum.
High Superheat: (starving)
In
this scenario, the compressor will get too hot causing its sump oil to
overheat, slowly break down and lose its viscosity (lubricating effect). If you
don’t have the correct lubricating effect, the compressor bearing will wear and
eventually seize.
Low Superheat (flooding)
In
this scenario, there is too much refrigerant coming back. Some say that these
new scroll compressors can withstand liquid flooding, which they can, but it’s
the oil that can’t.
What
happens is the sump oil becomes diluted with the refrigerant and loses its
viscosity (lubricating effect). If you don’t have the correct lubricating
effect, the compressor bearing will wear and eventually seize.
Points to note:
1. Bearing failure often gets reported as a winding
failure because the resulting locked rotors high current draw can cause the
winding to short out. Its not until the compressor is cut open for inspection
that you realize the seized bearing caused the winding to blow.
2. Superheat should be checked after the compressor
has run continually for at least ten minutes to allow the system refrigerant
and oil to settle.
3. The indoor units return air temperature and airflow
should be as close to normal operating conditions as possible as well as the
outdoor ambient.
Checking Superheat
It
is preferred to set superheat in cooling cycle when the indoor return air
temperature is just above set point e.g 23ºC plus or minus a couple of degrees.
The target superheat temperature is generally 3ºC to 5ºC (4ºC to 6ºC for EEV’s)
1. Fit your LP gauge to the common suction line port
situated between the compressor and the reversing valve.
2. Convert this Low Pressure to temperature using a
pressure/temperature conversion chart or the relevant refrigerant temperature
scale on your manifold gauge.
3. Measure the temperature of the suction line as it
enters the condensing unit with an “accurate” digital thermometer.
4. Subtract the converted pressures temperature away
from the pipe surface temperature and that’s the superheat.
Example
1: If the R410A units low pressure was
755kpa and the suction pipe temperature was 12ºC then: 755kpa converted to
temperature is 2ºC so we then subtract 2 from the 12ºC pipe temperature which
results in a superheat of 10ºC. Indicating in this case it’s a little high and
requires lowering.
Example
2: If the R22 units low pressure was
380kpa and the suction pipe temperature was 4ºC then: 380kpa converted to
temperature is -1ºC so the difference between this -1 and the 4ºC pipe
temperature is a superheat of 5ºC Indicating in this case it is OK.
Adjusting superheat
TX Valve
Wind
the valve stem IN to increase or wind it OUT to decrease, then wait
approximately ten minutes for it to settle before rechecking.
Accurators
Add
refrigerant to decrease Superheat or Remove refrigerant to increase Superheat,
then wait approximately ten minutes for the system to settle before rechecking.
EEV
Electronic
expansion valves can only be adjusted by changing their internal program
parameters which are usually factory set and chances are the problem is lack of
system refrigerant or a fault elsewhere.
There
are many influences associated with superheat like evaporator airflow,
evaporator return & supply air temperatures and condensing temperature. So
if you’re unsure, you need to contact the relevant supplier for technical
information.
Compressor
Discharge Pipe Temperature (hot gas)
The
compressor discharge pipe temperature is in direct relationship to the
superheat. A ball park figure is that this temperature on a scroll compressor
is usually 60ºC to mid 70’s when the superheat is acceptable and the operating
conditions are normal.
As
a crude rule of thumb, you will find that if the discharge pipe is cool enough
to hold your hand on then you can almost guarantee that the refrigerant is
flooding back (0ºC superheat). If it’s too hot to touch, then its superheat is
probably too high (starving).
You
should be able to touch the compressor discharge pipe for about half a second
before the heat is unbearable. Next time you set the superheat, measure the
discharge temperature and after a few settings you should see a pattern emerge